Personnel Safety Interlock (PSI) System

🔒 Closing the Hutch Door 

image.png
image.png
  1. Press the orange "Search" button

  • Beacon flashes orange & green

  • The alarm sounds for 15 seconds

2. Ensure all personnel exit the hutch

image.png

1

2

3. Close and lock the hutch door

Turn key anticlockwise to 12 o’clock

4. Insert key into door lock slot and turn to ON

  • Must complete within 15 seconds 

  • Beacon turns orange if successful

  • If timeout: beacon turns green → restart from step 1

image.png

1

image.png

2

image.png

5. Press green "ON" button on magnetic door lock

image.png

1

image.png

2

6. Push door firmly closed

  • Green light = magnetic lock engaged

  • Red light = lock failure → PSI blocks shutter

image.png
image.png

7. Turn on MBS

  • Confirm "X-RAY ON" light is lit

  • Beacon turns red